Petroleum Storage Tank Fire Protection System
Features:
Specifications:
Foam Chambers are air aspirating devices used for the protection of fixed roof flammable liquid storage tanks. Foam chambers are widely used in low expansion foam system .
Model no. |
Inlet |
Outlet |
Flow @ 3 Bar |
BEW/50 |
50 NB |
80 NB |
75-225 LPM |
BEW/65 |
65 NB |
100 NB |
225-450 LPM |
BEW/80 |
80 NB |
150 NB |
450-900 LPM |
BEW/100 |
100 NB |
200 NB |
900-1800 LPM |
BEW/150 |
150 NB |
250 NB |
1800-2700 LPM |
Material |
Mild Steel |
||
Vapour seal rupture pressure |
0.7 to 1.75 Bar |
||
Flange connection |
As per requirement |
||
Finish |
Fire Red |