Technical specification:-
Operating procedure |
Inlet pressure |
Total water flow (GPM) |
By-Pass flow (GPM) |
Expanded foam (M/min) |
Expansion |
By-Pass valve Closed |
7 bar |
240 litres/min |
nil |
136 |
500-725 |
By-Pass valve Fully Open |
7 bar |
265 litres/min |
100 litres/min |
150 |
800-1100 |
By-Pass valve Fully Open |
10 bar |
315 litres/min |
115 litres/min |
200 |
800-1100 |